Please wait a minute...
J Chin Soc Corr Pro  1985, Vol. 5 Issue (4): 270-276    DOI:
Current Issue | Archive | Adv Search |
COORDINATED EDTA CLEANING OF BOILER--A NEW TECHNIQUE
Zhang Bolin The Research Department of Southwest Management Bureau of Power Industry
Download:  PDF(513KB) 
Export:  BibTeX | EndNote (RIS)      
Abstract  The reaction of boiler scale with EDTA aqueous solution under elevated temperature is a complex reaction,but is an acid-base reaction as well. By controlling appropriate conditions,the pH value of the cleaning liquid may automatically rise,from weakly acidic to weakly basic state for the descaling of scale.A new technique called coordinated EDTA cleaning of boiler has been worked out which completes boiler cleaning and inactivation in one step. This technique for boiler cleaning has the following advantages: (1)the cleaning system is simple and more convenient to control, (2)there is less water consumed,(3)it shortens cleaning time, (4)pollution is minimized.
Received:  25 August 1985     
Service
E-mail this article
Add to citation manager
E-mail Alert
RSS
Articles by authors

Cite this article: 

Zhang Bolin The Research Department of Southwest Management Bureau of Power Industry. COORDINATED EDTA CLEANING OF BOILER--A NEW TECHNIQUE. J Chin Soc Corr Pro, 1985, 5(4): 270-276.

URL: 

https://www.jcscp.org/EN/     OR     https://www.jcscp.org/EN/Y1985/V5/I4/270

[1] 杨德俊,《络合滴定的理论和运用》,国防工业出版社,(1965)
[2] Muvphy,V.P.,Combustion,50(11) ,(1979)
[3] 和田洋六,酸洗净废液处理,火力原子力发电,28(8) ,(1977)